HAT72 ATS Control
HAT72 is an Automatic Transfer Switch Control Module. The module features 8-Bit microprocessor control. The module is used to monitor two single-phase AC supply. Once mains AC supply failure is detected (under voltage, over voltage, under frequency, over frequency), The module will control generator to start. If generator AC can load, The module Automatically transfer the switch to generator AC supply,
●FEATURES
◇Micro-processor based design;
◇Meter two single-phase AC Voltages;
◇Set AUTO or MANUAL via PUSHBOTTON mounted on the front panel;
◇Two isolable N designed;
◇7 LEDs display the status;
◇Operational timers can be altered by PC;
◇Control generator to Start;
●SPECIFICATION
◇DC supply: 9 to 35V(1.5VA)
◇single-phase AC input: AC30~300V(+20%) 50/60Hz
◇Relay output:
Relay of close mains amp; close gens: 16A 250VAC
Relay of start generator: 10A 250VAC
◇Delay timers:
Mains Normal delay time: 0~3600s
Mains Abnormal delay time: 0~3600s
Gens Normal delay time: 0~3600s
Start generator time:0~3600s(after Mains is abnormal)
Stop generator time:0~3600s(after Mains is normal)
Close time:0~20.0s
Over close time: 0~5.0s
Between close time: 0~3600s
◇Critical value
Mains under voltage:0~360V
Mains over voltage:0~360V
Gens under voltage:0~360V
Gens over voltage:0~360V
Gens under frequency: 0~60.0Hz
Gens over frequency:40.0~75.0Hz
◇Accessorial input
state can be altered by PC
◇Operating Temperature Range:
-20 to +70°C